UPSI-2406R2DP1MB Intelligent DC-UPS / DIN Rail / USB / RS485 / 144W / 24V 6A / LiFePO4 Battery 33Wh / DC-DC / accu
Uninterruptible power supply (DC UPS) with integrated Li-Ion Battery for DIN Rail
- Operating temperature range 0...+50°C
- Li-Ion battery pack with IEC 62133-2 safety certification
- USB-C & RS485 Modbus Interface
- Intelligent power sharing
- Regulated output voltage in backup mode
- Minimum load detection
- Power fail Timer-Function
- Relay dry contact on power fail
- Plug&Play - recognized as UPS by operating system
- Extended functionality by UPScom management software
- Shutdown & Reboot function
- Approved to IEC/EN/UL 61010-1 / -2-201
Shipping weight: 0.534 kg
Next-gen DC UPS solution “Made in Germany”:
24V / 6A backup power supply with Li-ion technology, USB-C and RS485 Modbus
The UPSI-2406R2DP1MB represents the latest generation of intelligent DC UPS systems for DIN rail mounting – engineered for maximum availability, high power density and long service life. It reliably protects control and automation applications against power failures, voltage dips and flicker.
In contrast to conventional lead-acid battery-based UPS solutions, this version features an integrated lithium-ion battery that enables particularly powerful, compact and long-lasting bridging of DC loads. Thanks to the optimised power electronics, connected loads are supplied reliably at all times, effectively preventing costly downtime and data loss.
The extended operating temperature range and comprehensive protection features ensure stable operation even in demanding industrial environments. Front-side USB-C and RS485 Modbus interfaces allow seamless integration into existing control architectures and convenient monitoring via the UPScom management software. Enhanced protection mechanisms and improved surge & burst immunity provide additional operational safety.
The compact UPSI-2406R2DP1MB in a robust DIN rail housing is ideal for long-term use in control cabinet applications and decentralised power concepts. It ensures reliable protection for embedded IPCs, controllers, motor drives, sensors as well as measurement, control and safety technology.
Increased Surge & Burst immunity and comprehensive protection functions
The 24V DC UPS offers high immunity against fast transients (burst) and surge voltages. It complies with standards EN 61000-4-4 and EN 61000-4-5, with test voltages of up to 2kV for burst tests and up to ±0.5kV (L–N) and ±1kV (L–PE, N–PE) for surge tests, each with test criterion A. This ensures reliable operation even in electromagnetically demanding environments.
In addition, the emergency power supply is equipped with extensive protection functions, including reverse polarity protection, short-circuit protection, and overcurrent protection. These features ensure maximum operational safety, extend the service life of connected devices, and minimize failure risks in critical applications.
What are the advantages of Lithium-Ion technology?
In terms of system integration and economy (TCO), Lithium-Ion cells enable energy storage devices with space and weight savings of up to 75% – compared to conventional lead-acid batteries. Lithium is the lightest metal in the periodic table and has ideal electrochemical properties for providing high specific energy densities (Wh/kg). Also many times higher than with lead-acid batteries is the number of charging cycles and the realizable Depth of Discharge (DoD). Finally the service life under comparable operating conditions is up to five times longer.
'Power Sharing' with intelligent input current detection
The intelligent PowerSharing at 24VDC input ensures that the upstream AC/DC power supply does not have to be overdimensioned, because the input power is kept constant and appropriately distributed to load and Li-Ion battery charger. With a low load at the output, more energy flows into the charger and vice versa. This saves energy and costs.
'Smart Battery Lock' prevents battery discharge
The battery management system prevents the integrated battery pack from leakage discharging when the UPSI-2406DP1 is switched off by deactivating the battery accordingly. By reducing the BMS own power consumption to a minimum, safety and shelf life of the DC UPS also increases significantly.
With help of the integrated load sensor, the DC UPS is switched off as soon as the load value falls below the threshold (no load) so that energy is not used unnecessarily.
UPS management software 'UPScom'
with intuitive user interface
The software 'UPScom' (freely available for download) allows the connected devices to be shut down and switched off in a controlled manner during a power failure in order to avoid data loss or damage. The responsive WEB UI is called up in a web browser to set and pre-program all parameters of the DC UPS system and for real-time monitoring with state-of-charge indicator. The adjustable parameters include, among other things, load sensor (mA), shutdown delay, maximum backup time, minimum charge capacity before system start, notifications by email.
Cross-platform technology
'UPScom' uses the new WebAssembly (WASM) architecture, which runs in most current web browsers. 'UPScom' runs on x86 compatible systems and also on most ARM-64 based systems under Microsoft® Windows and various Linux distributions.
Secure Shutdown & Reboot function for IPC systems
In the event of a "power failure", the UPS signals the failure of the supply voltage via the integrated interfaces, so that a controlled shutdown of the computer system is initiated and valuable data is saved. A script (batch) can also be executed before the system is shut down in order to process your own application-relevant processes. The integrated reboot function of the DC UPS automatically restarts the supplied IPC after the supply voltage returns, without the need for time-consuming on-site intervention by a service employee, e.g. in the case of completely self-sufficient computer systems at inaccessible locations.
Email messenger service
'UPScom' can be used for various events such as loss of connection to the UPS, system shutdown or power failure. These preventative measures can reduce or eliminate downtime.
Maximum safety for your 24 VDC application
In the field of uninterruptible power supply, our DC UPS systems can be used in a variety of applications for a wide range of industries: Industry 4.0, automation, medical and laboratory technology, transportation, traffic monitoring, energy, communication, vending, POS / payment systems, security technology and many more.
Customer-specific solutions and adjustments for your individual application are possible on request. We are happy to help!
Next-gen DC UPS solution “Made in Germany”:
24V / 4A backup power supply for cost-sensitive applications offers Li-ion technology, USB-C and RS485 Modbus
The UPSI-2406R2DP1MB represents the latest generation of intelligent DC UPS systems for DIN rail mounting – engineered for maximum availability, high power density and long service life. It reliably protects control and automation applications against power failures, voltage dips and flicker.
In contrast to conventional lead-acid battery-based UPS solutions, this version features an integrated lithium-ion battery that enables powerful, compact and reliable bridging of DC loads. Thanks to the optimised power electronics, connected loads are supplied reliably at all times, effectively preventing costly downtime and data loss.
The extended operating temperature range and comprehensive protection features ensure stable operation even in demanding industrial environments. Front-side USB-C and RS485 Modbus interfaces allow seamless integration into existing control architectures and convenient monitoring via the UPScom management software. Enhanced protection mechanisms and improved surge & burst immunity provide additional operational safety.
The compact UPSI-2406R2DP1MB in a robust DIN rail housing is ideal for long-term use in control cabinet applications and decentralised power concepts. It ensures reliable protection for embedded IPCs, controllers, motor drives, sensors as well as measurement, control and safety technology.
UPS management software 'UPScom'
with intuitive user interface
The software 'UPScom' (freely available for download) allows the connected devices to be shut down and switched off in a controlled manner during a power failure in order to avoid data loss or damage. The responsive WEB UI is called up in a web browser to set and pre-program all parameters of the DC UPS system and for real-time monitoring with state-of-charge indicator. The adjustable parameters include, among other things, load sensor (mA), shutdown delay, maximum backup time, minimum charge capacity before system start, notifications by email.
Cross-platform technology
'UPScom' uses the new WebAssembly (WASM) architecture, which runs in most current web browsers. 'UPScom' runs on x86 compatible systems and also on most ARM-64 based systems under Microsoft® Windows and various Linux distributions.
Secure Shutdown & Reboot function for IPC systems
In the event of a "power failure", the UPS signals the failure of the supply voltage via the integrated interfaces, so that a controlled shutdown of the computer system is initiated and valuable data is saved. A script (batch) can also be executed before the system is shut down in order to process your own application-relevant processes. The integrated reboot function of the DC UPS automatically restarts the supplied IPC after the supply voltage returns, without the need for time-consuming on-site intervention by a service employee, e.g. in the case of completely self-sufficient computer systems at inaccessible locations.
Email messenger service
'UPScom' can be used for various events such as loss of connection to the UPS, system shutdown or power failure. These preventative measures can reduce or eliminate downtime.
What are the advantages of Lithium-Ion technology?
In terms of system integration and economy (TCO), Lithium-Ion cells enable energy storage devices with space and weight savings of up to 75% – compared to conventional lead-acid batteries. Lithium is the lightest metal in the periodic table and has ideal electrochemical properties for providing high specific energy densities (Wh/kg). Also many times higher than with lead-acid batteries is the number of charging cycles and the realizable Depth of Discharge (DoD). Finally the service life under comparable operating conditions is up to five times longer.
'Power Sharing' with intelligent input current detection
The intelligent PowerSharing at 24VDC input ensures that the upstream AC/DC power supply does not have to be overdimensioned, because the input power is kept constant and appropriately distributed to load and Li-Ion battery charger. With a low load at the output, more energy flows into the charger and vice versa. This saves energy and costs.
'Smart Battery Lock' prevents battery discharge
The battery management system prevents the integrated battery pack from leakage discharging when the UPSI-2406DP1 is switched off by deactivating the battery accordingly. By reducing the BMS own power consumption to a minimum, safety and shelf life of the DC UPS also increases significantly.
With help of the integrated load sensor, the DC UPS is switched off as soon as the load value falls below the threshold (no load) so that energy is not used unnecessarily.
Maximum safety for your 24 VDC application
In the field of uninterruptible power supply, our DC UPS systems can be used in a variety of applications for a wide range of industries: Industry 4.0, automation, medical and laboratory technology, transportation, traffic monitoring, energy, communication, vending, POS / payment systems, security technology and many more.
Customer-specific solutions and adjustments for your individual application are possible on request. We are happy to help!
Increased Surge & Burst immunity and comprehensive protection functions
The 24V DC UPS offers high immunity against fast transients (burst) and surge voltages. It complies with standards EN 61000-4-4 and EN 61000-4-5, with test voltages of up to 2kV for burst tests and up to ±0.5kV (L–N) and ±1kV (L–PE, N–PE) for surge tests, each with test criterion A. This ensures reliable operation even in electromagnetically demanding environments.
In addition, the emergency power supply is equipped with extensive protection functions, including reverse polarity protection, short-circuit protection, and overcurrent protection. These features ensure maximum operational safety, extend the service life of connected devices, and minimize failure risks in critical applications.
| Output voltage: | 24VDC |
| Output current max. convection cooled in A: | 4 |
| Input voltage: | DC |
| Input voltage DC in V: | 24 |
| Mounting: | DIN-Rail |
| Output power in W: | 96 |
| UPS storage medium: | Li-Ion |
Feel free to contact us at [email protected].
WEEE-Nr: DE18400369
- Ultra slim design
- Operates from -40°C to +70°C
- Compliance with DOE VI Energy Standard
- Ultra slim design
- Operates from -40°C to +70°C
- Compliance with DOE VI Energy Standard
- Ultra-compact size
- Full power from -10°C to +55°C operation
- Extreme low temperature cold start at -40°C
- Active PFC with up to 92% efficiency
- Power Boost of 150% up to 7 seconds
- Maritime approvals GL / ABS
- DC UPS with Li-Ion battery inside
- Minimum load detection
- Power-fail Timer
- Approved to IEC/EN/UL 61010-1
- DC UPS with LiFePo4 battey inside
- Operating temperature range -20…+50°C
- USB-C and RS485 Modbus Interface
- With UPScom management software
- DC UPS with Supercaps inside
- Operating temperature range -20...+65°C
- USB-C and RS485 Modbus Interface
- With UPScom management software
- Integrated LiFePO4 battery
- Regulated output voltage in backup mode
- USB-C & ModBus interface
- Reboot function
- DC UPS with Supercaps inside
- Operating temperature range -20...+65°C
- Power-fail Timer
- Approved to IEC/EN/UL 61010-1
- Integrated maintenance-free Supercaps
- Regulated output voltage in backup mode
- USB-C & ModBus interface
- Reboot function
- DC UPS with LiFePo battery inside
- Operating temperature range -20…+50°C
- Power-fail Timer
- With UPScom management software
- Compact 24V DC-UPS
- Integrated Supercaps - maintenance-free
- UPScom manegment software incl.
- Reboot function
- Flexible DC-UPS for LiFePo and SuperCaps
- USB and RS232 interface
- Incl. UPScom management software
- Advanced battery protection
- Flexible DC-UPS for LiFePo and SuperCaps
- USB and RS232 interface
- Incl. UPScom management software
- Advanced battery protection
- DC UPS with LiFePo battery inside
- Powerful and reliable
- USB and RS232 Interface
- Operating temperature range -20°…+55°C
- Outdoor AC/DC UPS for extreme environments
- Integrated LiFePO4 energy storage (330 Wh)
- Temperature range -20…+50°C
- DC UPS with LiFePo battery inside
- Operating temperature range -20...+55°C
- USB & RS232 Interface
- Incl. UPScom management software
- Outdoor DC UPS
- Protection class IP65 / IP67
- Battery capacity 99Wh
- Operating temperature range -20...+55°C
- Outdoor DC UPS
- Protection class IP65 / IP67
- Battery capacity 33Wh
- Operating temperature range -20...+50°C
- Flexible DC-UPS for LiFePo and SuperCaps
- USB and RS232 interface
- Incl. UPScom management software
- Advanced battery protection
- DC UPS with Supercaps inside
- Operating temperature range -20...+65°C
- USB & RS232 Interface
- Incl. UPScom management software
- Fanless design for conduction cooling
- Selectable output +12V, +19V or +24VDC
- Very high efficiency up to 98%
- 3 years warranty
- LiFePO4 battery pack
- Safe, reliable and durable
- Extended temperature range
- IEC 62133-2 safety certification
- Compact 24V DC-UPS
- Supercaps - maintenance-free
- Software UPS Control Center
- Extended temperature range
- Ultra wide input range 6…36 V DC
- Temperature range from -20...+70°C
- High efficiency up to 94 %
- Designed according ATX3.0
- DC-UPS for lead acid batteries
- Zero switch over time from loss of DC input
- Operating temperature range -20°C to +60°C
- Low budget UPS solution
- Ultra slim design
- Operates from -40°C to +70°C
- Compliance with DOE VI Energy Standard
- Flexible DC-UPS for LiFePO4 and SuperCaps
- USB and RS232 interface
- Incl. UPScom management software
- Advanced battery protection
- DC UPS with 24V input and 12V output
- SuperCaps as energy storage
- Maintenance-free and fanless
- Interface RS232 & I²C
- Outdoor DC UPS
- Protection class IP65 / IP67
- Robust aluminium housing
- Operating temperature range -20...+50°C
- DC UPS with 24V input and 12V output
- SuperCaps as energy storage
- Maintenance-free and fanless
- Interface RS232 & I²C
- LiFePO4 battery pack (DIN rail)
- Safe, reliable and durable
- Extended temperature range
- IEC 62133-2 safety certification
- DC-UPS for lead acid batteries
- Operation temperature range from -20°C to +60°C
- Full corrosion resistant Aluminium chassis
- Low budget UPS solution
- Compact 12V DC-UPS
- Integrated Supercaps - maintenance-free
- UPScom management software incl.
- Reboot function
- LiFePO4 battery pack (DIN rail)
- Safe, reliable and durable
- Extended temperature range
- IEC 62133-2 safety certification
- DC UPS with 24V input and 12V output
- SuperCaps as energy storage
- Maintenance-free and fanless
- Interface RS232 & I²C
- LiFePO4 battery pack
- Extended temperature range -20…+55°C
- Very high storage capability
- Ideal for long-term backups
- IEC/EN and UL 62133-2 approved
- System present function
- Integrated temperature sensor
- High energy density
- Flexible DC-UPS for LiFePo and SuperCaps
- USB and RS232 interface
- Incl. UPScom management software
- Advanced battery protection
- Compact 12V DC-UPS
- Supercaps - maintenance-free
- Software UPS Control Center
- Reboot function
- Flexible DC-UPS for LiFePO4 and SuperCaps
- USB and RS232 interface
- Incl. UPScom management software
- Advanced battery protection
- Ultra slim design
- Operates from -40°C to +70°C
- Compliance with DOE VI Energy Standard
- Integrated, space-saving UPS solution
- USB interface
- Reboot function
- Wall bracket available
- LiFePO4 battery pack
- Safe, reliable and durable
- Extended temperature range
- IEC 62133-2 safety certification